JimW, JeffK, HughR
Around 1900 utc, the pressure dropped and the servo drive went to max; from afar, this looks like a fluid level trip. Jeff went to the end station and found that the front panel red light was still on indicating it was not a fluid level trip. Opening the controller panel to access the VFD revealed the OU3 error indicator. Last aLog with this problem found with quick search was at EndY July 2015. Maybe it is a warmer weather problem. Brought control servo output to 0, reset VFD to clear the error and then brought things back under servo control, around 2200utc. Jeff noted the fluid levels were same as before--no fluid problems.
According to the manual OU3 is an "over voltage error while at constant speed". - see attached page.
Other VFDs on site have similar issues which we think is due to spikes on the 3 phase supply.
Richard can tell you more.