filiberto.clara@LIGO.ORG - posted 17:17, Wednesday 03 August 2016 - last comment - 10:48, Friday 05 August 2016(28857)
Y2-8 HV Ion Pump Cable Repaired
The HV power cable for the Y2-8 ion pump has been repaired. The damaged section was cut off, and the cable was spliced together. Cable was tested with the HI-POT tester to 5KV.
Comments related to this report
gerardo.moreno@LIGO.ORG - 17:23, Wednesday 03 August 2016 (28859)
Connected cable to controller and turned ion pump on. Pump is pumping now, see attached for 3 hour trend data.
Work done under WP #6047 and FRS ticket 5992 closed