Displaying report 1-1 of 1.
Reports until 12:23, Wednesday 24 August 2016
H1 CDS
david.barker@LIGO.ORG - posted 12:23, Wednesday 24 August 2016 - last comment - 13:23, Wednesday 24 August 2016(29280)
models using the cdsEzca read and write parts

Daniel and Vern asked for a list of H1 models which are using the cdsEzcaRead and cdsEzcaWrite parts to transfer data to remote IOCs. This is following my discovery that the h1psliss model is attempting to send data to LLO EPICS channels (which also do not exist at LLO, presumably obsolete channels).

To make the list, I created a list of front end model core mdl files and grep within each file (grep -B 2 cdsEzCaWrite */h1/models/${model}|grep ":")

cdsEzCaRead:

h1ioppemmx.mdl *

      Name       "H1:DAQ-DC0_GPS"

h1ioppemmy.mdl *

      Name       "H1:DAQ-DC0_GPS"

h1sushtts.mdl 

      Name       "H1:LSC-REFL_A_LF_OUTPUT"

h1pslpmc.mdl

 

      Name       "H1:PSL-OSC_LOCKED"

h1tcscs.mdl

      Name       "H1:ASC-X_TR_B_SUM_OUTPUT"

      Name       "H1:ASC-Y_TR_B_SUM_OUTPUT"

      Name       "H1:TCS-ETMX_RH_LOWERPOWER"

      Name       "H1:TCS-ETMX_RH_UPPERPOWER"

      Name       "H1:TCS-ETMY_RH_LOWERPOWER"

      Name       "H1:TCS-ETMY_RH_UPPERPOWER"

      Name       "H1:TCS-ITMX_CO2_LASERPOWER_ANGLE_CALC"

      Name       "H1:TCS-ITMX_CO2_LASERPOWER_ANGLE_REQUEST"

      Name       "H1:TCS-ITMX_CO2_LASERPOWER_POWER_REQUEST"

      Name       "H1:TCS-ITMX_CO2_LSRPWR_MTR_OUTPUT"

      Name       "H1:TCS-ITMX_RH_LOWERPOWER"

      Name       "H1:TCS-ITMX_RH_UPPERPOWER"

      Name       "H1:TCS-ITMY_CO2_LASERPOWER_ANGLE_CALC"

      Name       "H1:TCS-ITMY_CO2_LASERPOWER_ANGLE_REQUEST"

      Name       "H1:TCS-ITMY_CO2_LASERPOWER_POWER_REQUEST"

      Name       "H1:TCS-ITMY_CO2_LSRPWR_MTR_OUTPUT"

      Name       "H1:TCS-ITMY_RH_LOWERPOWER"

      Name       "H1:TCS-ITMY_RH_UPPERPOWER"

h1odcmaster.mdl

      Name       "H1:GRD-IFO_OK"

      Name       "H1:GRD-IMC_LOCK_OK"

      Name       "H1:GRD-ISC_LOCK_OK"

      Name       "H1:GRD-OMC_LOCK_OK"

 

      Name       "H1:PSL-ODC_CHANNEL_LATCH"

* mid station pem systems do not have IRIG-B timing, cdsEzCaRead is used to remotely obtain starting GPS time.

EzCaWrite:

h1psliss.mdl *

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_1_GAINSTEP"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_1_SET_1"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_1_SET_2"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_1_SET_3"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_2_GAINSTEP"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_2_SET_1"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_2_SET_2"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_2_SET_3"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_3_GAINSTEP"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_3_SET_1"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_3_SET_2"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_3_SET_3"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_4_GAINSTEP"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_4_SET_1"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_4_SET_2"

  Name   "L1:IMC-SL_QPD_WHITEN_SEG_4_SET_3"

h1pslpmc.mdl

      Name       "H1:PSL-EPICSALARM"

* all writes to L1 channels will be removed on next restart of PSL ISS model.

Comments related to this report
jeffrey.kissel@LIGO.ORG - 13:05, Wednesday 24 August 2016 (29281)AOS, DetChar, GRD, IOO, ISC, PSL, SUS
Tagging all subsystems that are nominal responsible for these models.
david.barker@LIGO.ORG - 13:23, Wednesday 24 August 2016 (29282)

Interestingly h1tcscs is cdsEzCaRead'ing some of its own EPICS channels. Looks like a copy-paste issue, I'll work with Nutsinee when she gets back.

Displaying report 1-1 of 1.