filiberto.clara@LIGO.ORG - posted 16:44, Tuesday 20 September 2016 (29848)
Demod Readback Signals

Fault 6024  Work Permit 6105

Continued troubleshooting the Demodulator readback signals for the green WFS at the end stations. Traced issues to faulty Beckhoff analog input terminals - EL3104.

EY - EL3104 Terminals 6 and 9 were replaced

EX - EL3104 Terminals 6, 7, 8 , and 9 were replaced. I don't expect all four units to be bad, but was easier to replace all four at once.

Units removed will be tested to see if we can reproduce/diagnose the problem. 

One thing to note is that the RF Mon channels at EY were not as stable as EX. The LO mon signals at EY (15dB) had a 3dB difference than EX (18dB). Not sure if this is an issue or just the state of each end station at the time of testing.