ECR E1600042 WP 6217; ECR E1500325 WP 6227
To Remove DACKILL elements from HAM ISIs and HEPIs:
HAM ISI
.) Removed DACKILL Widgets on WD Block--Attachment 1.
.) Removed DACKILL link from WD Block to the ERRMON Block--Attachment 2.
.) Routed WD_STATE from WD Block to ERRMON--Attachment 2.
.) Added WD_STATE Logic in ERRMON Block for Rogue Excitation Evaluation--Attachment 3.
HEPI
.) Removed DACKILL elements from HEPI (Top) Level--Attachment 4.
.) Removed DACKILL parts on WD Block--like ISI Attachment 1.
To update HEPIs to Bleedoff-Accumulated-Saturations feature running on ISIs for months:
.) Add WINDOWTIME inputs on HEPI WD Block--Attachment 5.
.) Removed Test Point pickoffs WD Flag channels--also on Attachment 5.
.) Replace model saturation counter on WD/IPS, L4C & ACT Blocks with WD_SATCOUNT_vb.c counter & bleedoff Function--Attachment 6 becomes Attachment 7, e.g.
JimB restarted all these models after the build and install. Reisolation was not a problem. HAM2 did have one trip on CPS during 1st isolation attempt but it worked fine on the 2nd...
SVN COMMITS:
/opt/rtcds/userapps/release/isi/common/models/
hugh.radkins@opsws1:models 0$ svn commit -m "Removed DACKILL remenants & wired WD_STATE to ERRMON"
Sending models/isihammaster.mdl
Transmitting file data .
Committed revision 14424.
/opt/rtcds/userapps/release/hpi/common/models
hugh.radkins@opsws1:models 0$ svn commit -m "Added sensor/actuator WD Saturation Bleedoff ala ISI & removed Test Point WD Flag channels"
Sending models/hepitemplate.mdl
Transmitting file data .
Committed revision 14425.
Still have some medm and SDF cleanup to do. In progress.
Yes I do know how to spell remnants!
I've edited the HEPI and ISI Watchdog medms getting rid of the DACKILL widgets that do not connect to anything now. Also added the IOP DACKILL to the HEPI screen which were absent. Also removed is the RESET ALL button as all it did was push the DACKILL and the RSET buttons. Only 1 WD reset button remains, RESET WD. CLEAR SATURATIONS ONLY button is on the ISIs, pretty self explanitory there. On the HEPIs, I elected to not add the Clear Saturations Only infrastructure as the RESET WD button will do the trick anyway and won't harm the platform if it is not tripped. The RESETs for the IOPDACKILL and the Rogue Exc WD on the ISIs still need to be done in addition to the RESET WD, if, the medms suggest (red) they need it. There is no Rogue Excitation Watchdog on the HEPIs.
I will commit these medms to the SVN when I confirm that LLO does not need the RESET ALL button.