Serviced Compressors #3, #4, and #5 at Y-End Vent/Purge-Air Skid

(Kyle, Gerardo)

Today compressors #3, #4, and #5 were all greased and pressure tested.

All compressors passed their compression test, #3 at 120 psi, #4 at 120 psi, and #5 at 130 psi.
Then all compressors and electrical motors were greased.

All compressor assemblies were run tested after service was performed.

Work performed under WP#6257.