cdsutils avg giving weird results in guardian??

The results of cdsutils.avg() in guardian is sometimes giving us very weird values. 

We use this function to measure the offset value of the trans QPDs in Prep_TR_CARM.  At one point, the result of the average gave the same (wrong) value for both the X and Y QPDs, to within 9 decimal places (right side of screenshot, about halfway down).  Obviously this isn't right, but the fact that the values are identical will hopefully help track down what happened.

The next lock, it correctly got a value for the TransX (left side of screenshot, about halfway down), but didn't write a value for the TransY QPD, which indicates that it was trying to write the exact same value that was already there (epics writes aren't logged if they don't change the value). 

So, why did 3 different cdsutils averages all return a value of 751.242126465?

This isn't the first time that this has happened.  Stefan recalls at least one time from over the weekend, and I know Cheryl and I found this sometime last week. 

Images attached to this report
Comments related to this report
jameson.rollins@LIGO.ORG - 21:01, Monday 24 October 2016 (30832)

This is definitely a very strange behavior.  I have no idea why that would happen.

As with most things guardian, it's good to try to get independent verification of the effect.  If you make the same cdsutils avg calls from the command line do you get similarly strange results?  Could the NDS server be getting into a weird state?

jenne.driggers@LIGO.ORG - 21:11, Monday 24 October 2016 (30833)

On the one hand, it works just fine right now in a guardian shell.  On the other hand, it also worked fine for the latest acquisition.  So, no conclusion at this time.

jenne.driggers@LIGO.ORG - 01:03, Tuesday 25 October 2016 (30838)OpsInfo

This happened again, but this time the numbers were not identical.  I have added a check to the Prep_TR_CARM state that if the absolute value of the offsets are larger than 5 (normally they're around 0.2 and 0.3, and the bad values have all been above several hundred) then notify and don't move on. 

Operators:  If you see the notification Check Trans QPD offsets! then look at H1:LSC-TR_X_QPD_B_SUM_OFFSET and H1:LSC-TR_Y_QPD_B_SUM_OFFSET.  If you do an ezca read on that number and it's giant, you can "cheat" and try +0.3 for X, and +0.2 for Y, then go back to trying to find IR.

sheila.dwyer@LIGO.ORG - 21:10, Friday 28 October 2016 (30976)OpsInfo

This happened again to Jim, and Cheryl, today and caused multiple locklosses

I've commented out the averaging of the offsets in the guardian. 

We used to not do this averaging, and jsut rely on the dark offsets not to change.  Maybe we could go back to that.  

 

For operators, until this is fixed you might need to set these by hand:

If you are having trouble with FIND IR, this is something to check.  From the LSC overview sceen, click on the yellow TRX_A_LF TRY_A_LF button toward the middle oc the left part of the screen.  Then click on the R INput button circled in the attachment, and from there check that both the X and Y arm QPD SUMs have reasonable offsets.  (If there is not IR in the arms, the offset should be about -1*INMON)

Images attached to this comment
david.barker@LIGO.ORG - 09:10, Saturday 29 October 2016 (30994)

Opened as high priority fault in FRS: