Reports until 13:41, Tuesday 25 October 2016
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 13:41, Tuesday 25 October 2016 (30853)
Serviced Compressors #3, #4, and #5 at X-End Vent/Purge-Air Skid

Compressors #3, #4, and #5 were greased and pressure tested.

Compression test findings: #3 at 120 psi, #4 at 130 psi, and #5 at 110 psi.
All compressors and electrical motors were greased.

All relief valves passed their test.

All compressor assemblies were run tested after service was performed.

Work performed under WP#6277.