Reports until 18:02, Friday 05 November 2010
LHO FMCS
kyle.ryan@LIGO.ORG - posted 18:02, Friday 05 November 2010 (310)
CP7 dewar vapor pressure

Thoroughly thawed Y-end LN2 economizer valve with heat gun then tapped with hammer, turned adjuster screw fully cw then backed out (7) complete turns ccw need to increase LN2 vapor pressure to nominal 10 psi.

~1815 - shut down rotating pumps purge air compressor at Y-end until LN2 vapor pressure problem is resolved.