Displaying report 1-1 of 1.
Reports until 16:37, Tuesday 08 November 2016
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 16:37, Tuesday 08 November 2016 (31339)
Serviced Compressors #1 and #2 at X-MID Vent/Purge-Air Skid

Compressors #1 and #2 were greased and pressure tested @ X-MID station.
Compression test results:  #1 at 135 psi, and #2 at 130 psi.
All compressors and electrical motors were greased.

Both relief valves passed their test.

Both compressors were run tested after service was performed.

Work performed under WP#6309.