Reports until 22:03, Friday 09 December 2016
H1 PEM (PEM)
corey.gray@LIGO.ORG - posted 22:03, Friday 09 December 2016 (32408)
PSL #101 Dust Alarms

Since we've been having constant Dust Alarms for the PSL Enclosure (#101), looked into trends over the last 2 months (looked at #101, wind, and some FMCS/HVAC channels).  

Since the levels as they currently are I wanted to inch them up a little (by x2).  This will help to reduce the constant alarms we get and prevent us from ignoring them.  But it is a small enough bump that we'll still get them when we are at higher levels.  Since there has been no change post-cleaning on 12/5, Jeff should investigate the air filtration system for the PSL.  Do we have requirements for cleanliness levels for the PSL Enclosure? 

Alarm Setting Changes

0.3um:  MINOR:  70->140  &  MAJOR:  100->200

o.5um:  MINOR:  70->140  &  MAJOR:  100->200

Images attached to this report