Displaying report 1-1 of 1.
Reports until 06:05, Saturday 17 December 2016
H1 PEM (PEM)
travis.sadecki@LIGO.ORG - posted 06:05, Saturday 17 December 2016 - last comment - 11:37, Saturday 17 December 2016(32653)
Temps at EX, EY, MX, MY nonsensical

It's pretty cold on site this morning, but is it possible that the temperature sensors are past their limits?  See screenshot.

Images attached to this report
Comments related to this report
daniel.sigg@LIGO.ORG - 11:37, Saturday 17 December 2016 (32671)

Actually this looks more like a conversion error between signed and unsigned words for the Fahrenheit readbacks. If you subtract 2^16/10 from these numbers, it makes sense! Filed FRS 6963.