VEA Temperature Trend Check: Looks Good
J. Kissel, B. Gateley

As we begin to bring things back up today, following the restart checklist from the OPS Wiki, I've taken a trend of the past 6 days of VEA temperatures. All looks pretty stable, within 1 [deg C] over the course of the trend. Attached are trends in [deg C] and [deg F] for the relavent channels.

One thing to note: the entire LVEA average channels, 
    H0:FMC-LVEA_AVTEMP_DEGC
    H0:FMC-LVEA_AVTEMP_DEGF
shows a significant drop (see last attachment), because it's an average of *all* LVEA temperature zones, including the H2 PSL area, which has indeed dropped by ~1-2 [deg C] in the past few days. However, Bubba took a look at the metrics on the FMP windowes machine, and suggests all looks as well as he expected. We both don't know which zones are averaged in either system, so we think that the zones near the H1 PSL (Zone 5), BSC 1,2,3 (Zone 1A), and in the output arm (Zone 4) are better metrics for H1 (and correspond better to the FMP system's channels),
H0:FMC-CS_LVEA_ZONE5_DEGC (or DEGF)
H0:FMC-CS_LVEA_ZONE1A_DEGC (or DEGF)
H0:FMC-CS_LVEA_ZONE4_DEGC (or DEGF)