Reports until 17:39, Thursday 23 February 2017
LHO VE
chandra.romel@LIGO.ORG - posted 17:39, Thursday 23 February 2017 (34357)
CP8 fuse swap

Replaced CP8 fuses to fix LLCV actuator after discovering actuator not responding to manual stroke.

No fuse LED indicator lights were lit at vacuum rack in EX VEA, so I needed to use cell phone while laser locked (sorry!) to text Kyle for wiring diagram locations. I replaced both fuses. Old fuses test good. Guessing that during actuator modification on Tuesday when fuses were pulled and plugged back in there was a bad connection.

Images attached to this report