Displaying report 1-1 of 1.
Reports until 11:24, Friday 05 May 2017
H1 CDS (DAQ)
david.barker@LIGO.ORG - posted 11:24, Friday 05 May 2017 - last comment - 12:44, Friday 05 May 2017(36047)
Details of last night's storm related CDS restarts

MSR UPS reports going onto battery power three times during the storm:

5/4 20:44:09 On Batt
5/4 20:44:10 On Line
5/4 20:45:41 On Batt
5/4 20:45:42 On Line
5/4 21:49:46 On Batt
5/4 21:49:47 On Line

Both BRS machines at the end stations did not reboot or require code restarts.

The corner station Beckhoff computer (h1ecatc1) did not reboot (on ups power), the units at the end stations did reboot around 20:48. h1ecatx1 required a manual reboot at 22:25 to complete its code startup.

None of the three HEPI pump controller computers rebooted or needed code restarts.

MY weather station stopped operating 21:34 PDT, was restarted this morning.

All Front End Computers rebooted around 20:46, some multiple times. Report generated from h1fs0's NFS mount requests for /opt/rtcds:

20:45:11    h1pemmy
20:45:12    h1pemmx
20:45:15    h1sush2b
20:45:18    h1lsc0
20:45:20    h1oaf0
20:45:22    h1seib3
20:46:42    h1pemmy
20:46:44    h1seiey
20:46:44    h1seiex
20:46:45    h1susauxey
20:46:46    h1pemmx
20:46:46    h1iscex
20:46:46    h1sush2b
20:46:47    h1iscey
20:46:48    h1seib1
20:46:49    h1susauxex
20:46:49    h1seih23
20:46:50    h1susauxh56
20:46:50    h1lsc0
20:46:51    h1susb123
20:46:51    h1susauxh2
20:46:52    h1susauxh34
20:46:52    h1asc0
20:46:52    h1susauxb123
20:46:52    h1oaf0
20:46:53    h1seib3
20:46:53    h1seih16
20:46:53    h1seib2
20:46:54    h1psl0
20:46:54    h1sush56
20:46:55    h1seih45
20:46:57    h1sush34
20:46:57    h1sush2a
20:47:07    h1susex
20:47:09    h1susey
 

Comments related to this report
david.barker@LIGO.ORG - 11:33, Friday 05 May 2017 (36048)

Because h1psl0 and h1oaf0 were rebooted last night, we don't need to reboot these next week during the vent to clear their '208 days running' issue.

david.barker@LIGO.ORG - 11:34, Friday 05 May 2017 (36049)

No systems on UPS power saw any issues last night, this includes NFS file servers, networking, DAQ, GDS.

david.barker@LIGO.ORG - 12:44, Friday 05 May 2017 (36051)

from cdsfs0's NFS mount request logs, the following computers rebooted:

20:46:58    h1digivideo2.cds.ligo-wa.caltech.edu.
20:47:02    h1auxscript0.cds.ligo-wa.caltech.edu.
20:47:13    h1digivideo0.cds.ligo-wa.caltech.edu.
20:47:14    h1digivideo1.cds.ligo-wa.caltech.edu.
21:50:59    h1auxscript0.cds.ligo-wa.caltech.edu.
21:51:05    h1digivideo2.cds.ligo-wa.caltech.edu.
21:51:19    h1digivideo0.cds.ligo-wa.caltech.edu.
21:51:23    h1digivideo1.cds.ligo-wa.caltech.edu.

This agrees with these machines not on ups power. Looks like no control room workstations/FOM machines rebooted.

 

Displaying report 1-1 of 1.