chandra.romel@LIGO.ORG - posted 14:36, Tuesday 16 May 2017 - last comment - 16:18, Tuesday 16 May 2017(36213)
Troubleshooting x-beam manifold pressure discrepancy

[John, Chandra]

More investigation on leak hunt of x-beam manifold. Here's what we're trying now:

Images attached to this report
Comments related to this report
patrick.thomas@LIGO.ORG - 16:11, Tuesday 16 May 2017 (36217)
In regard to GV5 not showing as hard closed on the medm screen.

I looked at the Beckhoff code. It appears that I am just not seeing a change in signal (from 0 to 1) for the closed limit switch. Both the code and documentation agree that this should be LY terminal 2 channel 4.

On April 8 2015 Kyle reported that GV5 hard closed (https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=17748). I see this in the minute trends (attached). This is the most recent time I can find GV5 being hard closed from the alogs.

On April 26 2016 LY was upgraded to Beckhoff (https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=26803).

I guess we should check the wiring into the Beckhoff chassis?
Non-image files attached to this comment
patrick.thomas@LIGO.ORG - 16:18, Tuesday 16 May 2017 (36219)
From minute trends, the last time that GV5 hard closed is on March 14 2016.

https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=26065
Non-image files attached to this comment