We have been working to stabilize the temperatures, mostly at End Y because that is the station that has the completed FMCS controls. End X should be completed by the end of this week. During this process several changes have been made to various components such as the face/by-pass damper, cooling valve, chillers etc. Currently the changes have only been made to the End Y station where we were trying to maintain 68 degrees F. After several conversations with Jeff K. and some calculations made by Jeff, he has determined that a more suitable temperature for E Y would be ~64 degrees F. I have changed the set point in the E Y VEA to to 64 F. I will monitor the temperature closely tonight and hopefully this will have the correct effect on the suspensions. I also had an alarm on the Mid X supply fan this morning and upon further investigation, I found that someone had turned the fan off at the electrical disconnect. I restored the HOA switch to auto position and started the fan.