Reports until 12:10, Monday 22 May 2017
LHO VE
logbook/robot/script0.cds.ligo-wa.caltech.edu@LIGO.ORG - posted 12:10, Monday 22 May 2017 - last comment - 17:22, Monday 22 May 2017(36313)
CP3, CP4 Autofill 2017_05_22
Starting CP3 fill. TC A error. TC B error. Fill aborted.
Starting CP4 fill. LLCV enabled. LLCV set to manual control. LLCV set to 70% open. Fill completed in 2620 seconds. TC B did not register fill. LLCV set back to 36.0% open.
Images attached to this report
Comments related to this report
patrick.thomas@LIGO.ORG - 12:53, Monday 22 May 2017 (36317)
Dave, Patrick

It appears that the temperature of the CP3 thermocouples started above 40 deg C which the script to perform this fill takes as an error. That is, the script takes any reading from the thermocouples above 40 deg C as an indication that the thermocouple is not working correctly. We have created WP 6649 to increase this upper limit.
chandra.romel@LIGO.ORG - 13:12, Monday 22 May 2017 (36318)

Thanks!

kyle.ryan@LIGO.ORG - 14:28, Monday 22 May 2017 (36323)
Increased CP4's manual LLCV %open value from 36% to 37%.  

Will let new script run before altering CP3's value.
patrick.thomas@LIGO.ORG - 15:51, Monday 22 May 2017 (36326)
First run of updated script did not complete after an hour:

Starting CP3 fill. LLCV enabled. LLCV set to manual control. LLCV set to 50% open. Fill not completed after 3600 seconds. LLCV set back to 21.0% open.

Dave is rerunning it.
Images attached to this comment
patrick.thomas@LIGO.ORG - 16:01, Monday 22 May 2017 (36328)
Fill completed:

Starting CP3 fill. LLCV enabled. LLCV set to manual control. LLCV set to 50% open. Fill completed in 384 seconds. TC B did not register fill. LLCV set back to 21.0% open.

Images attached to this comment
kyle.ryan@LIGO.ORG - 17:22, Monday 22 May 2017 (36334)
I looked at CP3's exhaust discharge pressure and am convinced that it did overfill following the second running of the new script.  I increased CP3's LLCV %open to 22% up from 21%.  It is getting warmer this might be too conservative?