H1 CDS (DAQ)
david.barker@LIGO.ORG - posted 13:37, Monday 22 May 2017 (36320)
CDS summary

We are working several issues at the moment, here is an executive summary:

bogus second trend data: Some vacuum channels were showing bogus data in their second trends if data over Thursday lunchtime's DAQ restart is requested. Work around is to ask for data up to and beyond the restart time.

BACnet EPICS FMCS data froze around 1pm Sunday (fixed by restarting code)

CP3 overfill did not proceed, thermocouples out of -20C to +40C range (mid 40C). Code will be changed to increase upper limit to 60C. WP6649

Air compressors were turned off at both end stations, Alarm system reconfigured to ignore these channels (WP 6647)

 