Reports until 12:19, Tuesday 23 May 2017
H1 SUS (SEI)
jeffrey.kissel@LIGO.ORG - posted 12:19, Tuesday 23 May 2017 (36349)
H1 ITMX ISI ST2 Trips with H1 SUS R0 Damping OFF; Modified QUAD OVERVIEW to Make R0 a Little More Visible
J. Kissel, J. Warner

H1 ISI ITMX ST2 (not ST1 or HEPI) tripped last night at ~9:30 UTC (1179548979, May 23 2017 04:29:21 UTC, May 22 2017 21:29:21 PDT) because Jeff forgot to turn the Reaction Chain damping back on after completing its set of transfer functions (LHO aLOG 36335). 

In order to help non-Jeffs diagnose the issue, Jeff has moved the link to the reaction chain on the QUAD overview screens,
    /opt/rtcds/userapps/release/sus/common/medm/quad/
        SUS_CUST_QUAD_OVERVIEW.adl
        SUS_CUST_QUAD_ITM_OVERVIEW.adl
to the top center (essentially swapping the positions of the never-used hierarchy switch and the reaction chain screen link). I've also added inputs and outputs to the R0 damping loops surround the button to remind people that there's a control system there which occasionally needs attention.

The screens have been committed to the userapps repo.

P.S. This interaction between a full isolated ISI and an undamped chain of the QUAD is not new, it's just been a while since we've regularly taken the full suite of undamped TFs on any QUAD, and I've forgotten that one should put the ISI ST2 in DAMPED. And also I haven't used the matlab automated transfer function suite that does all the settings in so long that I fear it'll do more damage than good. In the limit of infinite IFO time and person power (e.g. between O2 and O3?) we'll resurrect that code.
Images attached to this report