Reports until 17:23, Thursday 25 May 2017
H1 CDS
patrick.thomas@LIGO.ORG - posted 17:23, Thursday 25 May 2017 - last comment - 17:44, Thursday 25 May 2017(36434)
h1ecaty1 IOC error, computer restarted

Jeff K., Dave B., Patrick T.

Explicit steps given for reference.

1. Jeff K. noted that the readbacks for the end Y ALS EPICS channels were turning white on the ALS overview screen.

2. The current time for each PLC on h1ecaty1 was still updating on the CDS overview screen (bottom left corner under Slow Controls).

3. I ran rdesktop -T 'h1ecaty1' -g 2048x1280 -x l h1ecaty1 to connect to h1ecaty1 using remote desktop.

4. I logged in as controls.

5. The IOC terminal was minimized. I opened it by clicking its icon on the taskbar (circled in attached screenshot).

6. There were no errors initially shown in the terminal.

7. I hit enter in the terminal. The error shown in the attached screenshot appeared.

8. I hit enter again. No further errors appeared.

9. I restarted the computer by double clicking the icon on the desktop labeled 'RESTART'.

10. The issue was resolved.

Images attached to this report
Comments related to this report
patrick.thomas@LIGO.ORG - 17:31, Thursday 25 May 2017 (36436)

The following is a list of commands to connect to various Windows machines using remote desktop:

end X BRS: rdesktop -T 'h1brsex' -g 2048x1280 -x l h1brsex

end Y BRS: rdesktop -T 'h1brsey' -g 2048x1280 -x l h1brsey

corner station Beckhoff: rdesktop -T 'h1ecatc1' -g 2048x1280 -x l h1ecatc1

end X Beckhoff: rdesktop -T 'h1ecatx1' -g 2048x1280 -x l h1ecatx1

end Y Beckhoff: rdesktop -T 'h1ecaty1' -g 2048x1280 -x l h1ecaty1

patrick.thomas@LIGO.ORG - 17:44, Thursday 25 May 2017 (36437)
Created FRS 8220.