WP 7031
alog 36571
A EL3104 analog input Beckhoff terminal was replaced from EtherCAT End Station Chassis 3. Alog 36571 reported CH3 & CH4 on terminal 7 showing an offset. Used a voltage calibrator to verify offset was from EL3104 terminal and not upstream.
Trend over the past 8 days. Nominal adjusted to 21.5 dBm.