Reports until 11:58, Friday 26 November 2010
LHO FMCS
kyle.ryan@LIGO.ORG - posted 11:58, Friday 26 November 2010 (377)
CP1
PID values accumulated during stuck needle valve period taking too long to clear. CP1 as low as 65% full yet PID output still at minimum value (5% for CP1)  -> Came in and filled CP1 in manual mode. Changed PID parameters to expedite clearing out of accumulated values then restored nominal PID parameters.  PID should be current and assume control.