Reports until 11:55, Monday 24 July 2017
H1 CDS
david.barker@LIGO.ORG - posted 11:55, Monday 24 July 2017 (37742)
cell phone alarm texter restarted to add chiller yard water pump status channels

John, Bubba, Dave:

WP7083

the cell phone alarm system was reconfigured and restarted to add the CS, EX and EY water pump status channels. In the  FMCS EPICS database there is a CALC record which performs an inclusive OR on the pump status. If at least one pump is running, the STATUS is ONE. If no pumps are running, the STATUS is ZERO. The alarm levels are HIGH=1.5, LOW=0.5. There is no delay in sending the cell phone texts when an alarm is triggered. This completes this WP.