Reports until 12:13, Monday 28 August 2017
H1 CDS (DAQ, SUS)
david.barker@LIGO.ORG - posted 12:13, Monday 28 August 2017 - last comment - 12:32, Monday 28 August 2017(38398)
h1susitmy and daq restart

Sheila, Dave:

Sheila corrected and restarted the h1susitmy model. The change required a DAQ restart, which was done.

2017_08_28 11:53 h1susitmy
2017_08_28 12:00 h1broadcast0
2017_08_28 12:00 h1dc0
2017_08_28 12:02 h1fw0
2017_08_28 12:02 h1fw1
2017_08_28 12:02 h1fw2
2017_08_28 12:02 h1nds0
2017_08_28 12:02 h1nds1
2017_08_28 12:02 h1tw1

Comments related to this report
jeffrey.kissel@LIGO.ORG - 12:32, Monday 28 August 2017 (38400)DetChar, ISC, SUS
The problem was a typo -- the ITMX FF control signals were going to both ITMX and ITMY. This is likely the cause of our poor ~20-200 Hz performance overnight. Now fixed and on our way back up through initial alignment.