Remainder of FMCS channels migrated to BACnet IOC
The remainder of the FMCS channels have been migrated from the IOC on h0epics to the new BACnet IOC on fmcs-epics-cds. I have stopped the FMCS IOC on h0epics. There is now just the IOC running on fmcs-epics-cds. I have updated the wiki instructions. Dave updated the channels in the DAQ and the autoBurt.req file. The corner station MEDM screens still need some updating. There are some invalid channels that need further investigation.
Comments related to this report
patrick.thomas@LIGO.ORG - 17:44, Wednesday 18 October 2017 (39083)
These are the channels that are currently invalid:

H0:FMC-LVEA_AVTEMP_DEGF: @bacnet11000 2 10 85
H0:FMC-LVEA_CONTROL_AVTEMP_DEGF: @bacnet11000 2 20 85
H0:FMC-CS_LVEA_AH_DSCHRG_1_DEGF: @bacnet11010 0 1 85
H0:FMC-CS_LVEA_AH_DAMPER_1_PC: @bacnet11010 2 8 85
H0:FMC-CS_LVEA_AH_COOLVALVE_1_PC: @bacnet11010 2 9 85
H0:FMC-CS_LVEA_AH_COOLTEMP_1_DEGF: @bacnet11010 0 10 85
H0:FMC-CS_LVEA_AH_MIXAIR_1_DEGF: @bacnet11010 0 2 85
H0:FMC-CS_LVEA_AH_AIRFLOW_1: @bacnet11010 2 124 85
H0:FMC-CS_LVEA_AH_PITCH_VANE_1_PC: @bacnet11010 2 250 85
H0:FMC-CS_LVEA_AH_FAN_STATUS_1: @bacnet11010 3 5 85
H0:FMC-CS_LVEA_AH_COOLVALVE_2_PC: @bacnet11010 2 9 85
H0:FMC-CS_LVEA_AH_COOLTEMP_2_DEGF: @bacnet11010 0 10 85
H0:FMC-CS_LVEA_AH_AIRFLOW_2: @bacnet11010 2 128 85
H0:FMC-CS_LVEA_AH_PITCH_VANE_2_PC: @bacnet11010 2 259 85
H0:FMC-CS_LVEA_AH_FAN_STATUS_2: @bacnet11010 3 6 85
H0:FMC-CS_OSB_AH_CLDDECKTEMP_DEGF: @bacnet11070 0 1 85
H0:FMC-CS_OSB_AH_HOTDECKTEMP_DEGF: @bacnet11070 0 1007 85
H0:FMC-CS_OSB_AH_COOLVALVE_5_PC: @bacnet11070 2 8008 85
H0:FMC-CS_OSB_AH_AIRFLOW_5: @bacnet11070 2 8124 85
H0:FMC-CS_OSB_AH_COOLVALVE_6_PC: @bacnet11070 2 8008 85
H0:FMC-CS_OSB_AH_AIRFLOW_6: @bacnet11070 2 8129 85
H0:FMC-CS_OSB_AH_PITCH_VANE_5: @bacnet11070 2 8035 85
H0:FMC-CS_OSB_AH_PITCH_VANE_6: @bacnet11070 2 8036 85
H0:FMC-CS_OSB_AH_HEATINGCOIL_9_PC: @bacnet11070 2 8037 85
H0:FMC-CS_OSB_AH_HEATINGCOIL_10_PC: @bacnet11070 2 8038 85
H0:FMC-CS_OSB_AH_FAN_STATUS_5: @bacnet11070 3 5 85
H0:FMC-CS_OSB_AH_FAN_STATUS_6: @bacnet11070 3 6 85
H0:FMC-LVEA_AHU1_DIS_RH_PCT: @bacnet11011 0 2 85
H0:FMC-LVEA_AHU1_OSA_RH_PCT: @bacnet11011 0 3 85
H0:FMC-LVEA_AHU1_SPACE_RH_PCT: @bacnet11011 0 1 85
patrick.thomas@LIGO.ORG - 18:36, Wednesday 18 October 2017 (39085)
It appears that all the channels in the database on devices 11000, 11010, 11070 and 11011 are invalid.