Starting at 7pm Sunday PST, the hourly autoburt backup of h1ecaty1 started to fail. The backup of h1ecaty1plc1 fails more times than it succeeds, the backup of plc1 and plc3 have always failed since 7pm.
The problem appears to be with the local EPICS Gateway running on the machine autoburt (a virtual machine on cdsproxmox). Restarting the gateway will cause a re-broadcast of autoburt's connections, so it will wait until the code-restart moratorium is lifted. In theory the Beckhoff slow controls settings are stored locally, and therefore a lack of a burt snapshot may not be critical.