Reports until 17:59, Tuesday 19 December 2017
H1 SUS
betsy.weaver@LIGO.ORG - posted 17:59, Tuesday 19 December 2017 - last comment - 16:23, Wednesday 20 December 2017(39827)
BSC 1 2 3 Chamber closeout work today

Today, Travis and I worked to closeout BSC 3 to finish out the set of chambers needing doors put on.  We:

 

Comments related to this report
jeffrey.kissel@LIGO.ORG - 16:23, Wednesday 20 December 2017 (39850)DetChar
I attach a screenshot of the pitch transfer function during the Ring Heater cable rubbing. I also include illustrative drawings and pictures of the rubbing site. 

In words -- the ring heater cables (CBL7 and CBL 8 of D1001517), exiting the QUAD lower structure, should be sandwiched between the two inner face plates (aka "figure eights", D060462). On this ITM, it is not, and for the first time, it escaped far enough out of its designated path that it started to lightly interfere with the bottom of the main chain's UIM base plate (D060376).

Attachments:
First -- (from D0901346) A side view of the full solidworks assembly of the quad. The face plates are the long vertical blue things that extend the length of the lower structure. The two in the middle are the inner face plates.

Second -- (from D1001838)An isolated view of the test-mass-side's inner face plate, with the fully assembled ring heater and cabling system.

Third -- (from G1100850) Another view of the test-mass-side's inner face plate, with the fully assembled ring heater and cabling system.

Fourth -- (from D0901346) A screenshot of the QUAD's solidworks eDrawing assembly, where I've hidden enough to show the ring heater cables, and made the face plates transparent. Naturally, the eDrawing is buggy, and the ring heater cables are displaced from where they're designed to be, and are actually interfering with the *reaction* chain's UIM base plate, but you get the point.

Fifth -- a picture Betsy / Travis took of the offending cable rubbing against the *main* chain UIM base plate.

Sixth -- (from D1001517) A screenshot of just the cable assembly to show what "CBL7" and "CBL8" are.

Seventh -- A screenshot of the Pitch transfer function. Blue and Black are nominal, normal transfer functions. Red was while this rubbing was happening. As expected from the modes shapes of the middle-frequency pitch modes nominally at 1.33 Hz, 1.59 Hz, and 1.98 Hz, that had so clearly shifted, we knew that something was (wrong / rubbing) (in / around) the middle masses -- the PUM / UIM. 
Images attached to this comment