WP7230
Richard, Sheila, Marc, Dave:
The ADC inputs to h1asc were remapped following the addition of the first ADC.
The PSL Bulls Eye photo-diode channels were remapped as-per E1600381 drawings. The 9pin DSUB cable for this PD was moved on the 6th AA chassis from the last 4 channels to the next-to-last 4 channels. The model's four segments were remapped to be in segment order and not ADC channel order (see attachment)
After the h1asc model was restarted:
the DAQ was restarted
the Bullseye Input Matrix was modified to switch SEG1 and SEG3 settings. We think the SEG2,4 settings are still correct.
the ISC_CUST_BULLSEYE.adl medm file was modified to correct the segment drawing (see attachment)