Reports until 15:22, Thursday 21 December 2017
H1 CDS (DAQ)
david.barker@LIGO.ORG - posted 15:22, Thursday 21 December 2017 - last comment - 15:58, Thursday 21 December 2017(39870)
DAQ restart, new h1asc, new safety ini, NDS remapping to frames and trends

The DAQ was restarted today to install several changes:

new h1asc code (see alog 39868)

latest H0EDCU_SAFETY.ini

new nds configurations

The NDS reconfigurations are:

h1nds0: New daqdrc file to serve h1ldasgw0's archived raw minute trends from its SATABOY RAID.

h1nds1 (the default nds): now NFS mounts h1ldaswg1's /frames-1 and /trend-1 exports (was temporarily serving h1ldasgw0 while the E18 upgrade was progressing). Also new daqdrc file to serve h1ldasgw1's archived raw minute trends from its SATABOY RAID.

After the restart the EDCU did not connect to many of h1ecaty1's EPICS channels. Remember that the hourly autoburt machine started having connection issues to h1ecaty1 over the weekend. The autoburt machine was rebooted today, which did not fix its connection problems. This coupled with the EDCU issues leads us to think a restart of the IOCs on h1ecaty1plc[1,2,3] is needed. We will see if this can be scheduled pre-holidays.

Comments related to this report
david.barker@LIGO.ORG - 15:58, Thursday 21 December 2017 (39873)

I have verified that raw minute trend data for times prior to May 2017 are now available (I trended a weather channel for all of 2016).