Reports until 15:53, Friday 19 January 2018
H1 CDS (CDS)
jonathan.hanks@LIGO.ORG - posted 15:53, Friday 19 January 2018 - last comment - 16:38, Friday 19 January 2018(40202)
SDF failing for CS ECAT PLC4
The process segfaults at startup.  The reason appears to be an enum that went out of bounds.  It was requesting a description string that did not exist.  This appears to be an issue only when the connection is first made and a determination is made if the enum should be treated as a string or a numeric value.

See FRS https://services.ligo-la.caltech.edu/FRS/show_bug.cgi?id=9749
Comments related to this report
jonathan.hanks@LIGO.ORG - 16:38, Friday 19 January 2018 (40205)
I branched the advLigoRTS code and implemented a fix.  It is being tested on the h1sysecatc1plc4sdf.

The h1sysecatc1plc4sdf is running.