Reports until 10:18, Thursday 25 January 2018
H1 SEI (OpsInfo)
jim.warner@LIGO.ORG - posted 10:18, Thursday 25 January 2018 (40273)
More updates to ISI config screen, more eq buttons

After Jenne's experience with the Kamchatka earthquake last night, I've added the requested seismic recovery button the ISI_CONFIG screen, shown on attached image. The new, green Recover EQ button is just above the old, red Very Large EQ button, and mostly just reverses the operations of the red button. If any platforms are tripped, you'll have to reset watchdogs. There's also a long standing issue of the HAM2&3 GS13 gains, which for some reason can't be stably managed by the ISI guardians, so there will be SDF differences after recovering from an bad earthquake. I've also added the low frequency Z blrms for EX&EY STS2s to the stripchart on the lower right. If all 4 channels (LSC-CPS, & 3x .03-.1hz gnd blrms) on that display are headed off the stripchart, it's a pretty good indication of a large earthquake arriving.

Images attached to this report