WP 7312 I updated and restarted the h0vacex and h0vacey PLCs to create separate sync units for each Inficon gauge. The X2-8 and Y2-8 Inficon gauges are still powered off, but no longer disabled in TwinCAT. With the addition of the separate sync units this no longer prevents the remainder of the system from running. I burtrestored both h0vacex and h0vacey to 6am local time this morning. The high voltage at each end station has likely tripped off and will need to be reset.