CP4 Dewar economizer valve adjusted

Adjusted CP4 Dewar pressure relief valve (aka economizer valve) by turning screw 2 turns clockwise to increase head pressure. It was at 12 psig with tank 62.1% full. This may help increase GN2 flow. However, the PSI document specifies a head pressure of 5 psig for regen exercise. 

It will take a day or so for the head pressure to stabilize to new setting.

Comments related to this report
chandra.romel@LIGO.ORG - 17:27, Thursday 08 March 2018 (40917)

Backed off and made it one turn instead on economizer valve.