david.barker@LIGO.ORG - posted 16:57, Monday 12 March 2018 (40974)
vacuum alarms reconfigured to support CP4 bake-out

Chandra, Dave:

The upper alarm level for H0:VAC-MY_CP3_TE202A_DISCHARGE_TEMP_DEGC was increased from 130C to 150C.

The Rate-of-Change system was modified to calculate the ROC of H0:VAC-MY_CP4_TE253A_REGEN_TEMP_DEGC

The ROC for this TE253A was added to the alarms system, with the upper/lower alarm levels the same as TE202A (+1.0CperHour and -1.0CperHour).

ROC and alarms were restarted to make these changes.