Reports until 16:57, Wednesday 14 March 2018
H1 CDS
david.barker@LIGO.ORG - posted 16:57, Wednesday 14 March 2018 (41013)
vac alarms customized to tonight's operating conditions

Kyle, Dave:

to prevent nuisance cell phone alarms for out-of-nominal conditions overnight, we have reconfigured the alarms:

H0:VAC-MY_CP4_TE253A_REGEN_TEMP_DEGC is running cool, reduced its LOW alarm limit from 70C to 0C

H0:CDS-ROC_VAC_MY_CP4_TE253A_REGEN_TEMP_DEGC_1HOUR_R is trending towards ambient at a rate higher than 1.0 CperHour. Increase alarm rates to +/- 5.0CperHour

H0:VAC-MY_CP4_253_REGEN_TEMP_ALRM_INTLK will be in alarm overnight. Sends its alarms to emails only, not to cell phones.