Displaying report 1-1 of 1.
Reports until 15:28, Tuesday 03 April 2018
H1 CDS (DAQ, PSL)
david.barker@LIGO.ORG - posted 15:28, Tuesday 03 April 2018 - last comment - 16:02, Tuesday 03 April 2018(41266)
CDS maintenace summary

New h1psliss model for production ISS outer-loop chassis

Keita, Ben, Dave, Richard, Fil:

I installed a new h1psliss model which supports the production ISS outer-loop chassis. Main changes are: no need to borrow ADC channels from FSS, no need to borrow DAC channels from PMC, PD[1-80]_DC channels removed, EXC output removed (instead excitation is summed with TXY output channel digitally).

Model and DAQ were restarted at 13:30. The restart delay was due to unknown compile problems encountered when trying to disconnect the EXC output channel from the ISS part. Because this is a common part, I put in a work-around which did not change the number of output ports.

The new ADC channel layout is defined in the wiki https://cdswiki.ligo-wa.caltech.edu/wiki/H1PSLISSModelAdcDacChannels

New Beckhoff code

Daniel, Patrick, Dave:

New DAQ chan lists for ecatc1plc[2,3,4] were installed this morning. Chiller work changed PLC2,3 and SQZ work changed PLC4.

Some SDF updates are outstanding.

 

Comments related to this report
david.barker@LIGO.ORG - 16:02, Tuesday 03 April 2018 (41271)

ecatc1plc4:

new SDF monitor list installed (h1sysecatc1plc4sdf restarted)

new channels in SDF have been accepted and monitored in snap file

new autoBurt.req file installed

Displaying report 1-1 of 1.