Displaying report 1-1 of 1.
Reports until 11:31, Thursday 03 May 2018
LHO VE
chandra.romel@LIGO.ORG - posted 11:31, Thursday 03 May 2018 - last comment - 09:46, Friday 04 May 2018(41820)
CP4 ramp down

Temperature ramp down on CP4 bake is looking good. Currently at 90C.

Images attached to this report
Comments related to this report
chandra.romel@LIGO.ORG - 13:28, Thursday 03 May 2018 (41825)

Pressure is dropping as CP4 cools:  3e-7 Torr. As Kyle pointed out, the read back from Inficon hot cathode/pirani full range gauge has been noisy ever since the pressure spike from turbo controller trip (we suspect these Japanese turbo controllers are extra sensitive to spikes in line voltage from power cycling nearby inductors (i.e. large variac), because the turbo + cart are plugged into a 480V step-down transformer supplying many 120V outlets). These gauges change emission current at 5.6e-6 Torr and cause a large step down in pressure, as observed in corner and end station volumes. This gauge stepped down at around 3e-6 Torr. Note that it has been exposed to relatively high temperatures for two months. Manufacture spec for bake out is 80C.

Attached are 30 day and 90 day trends.

Images attached to this comment
chandra.romel@LIGO.ORG - 09:46, Friday 04 May 2018 (41839)

Ramp down still looking good. Attached are temperature and pressure trends over 3 days.

Images attached to this comment
Displaying report 1-1 of 1.