After evicting a tiny snake out of the X-End VEA floor, it just didn't want to go, I went to check on the purge air skid. This system was having issues keeping up with the demand.
After shutting off 4 out of the 5 compressors found that we had 3 relief valves stuck open, wasting lots of air.
All 3 bad relief valves were replaced and the system appears to be healthier now, after 30 minutes of the skid running on all compressors the dew point was measured at -18.2 oC.