FRS 11049
After DaveB swapped the BIO card from the I/O chassis, we tested the switching and saw no change in the behavior: switch worked fine with python command and HAM2 failed the switch when attempted by guardian.
After the swap, I isolated the ISI where the gains remained in the SAFE state. The gain/whitening where then switched to the run state (analog gain & whitening) with the COMMANDS python script; this switch worked fine. I then modified the guardian code for HAM2 to do the switching and changed the requested state to damped and the the platform trip immediately when guardian changed the gain & whitening filters. Likewise when going back to isolated, the platform tripped when the filters were changed.
Bottom line, no change in behavior with the new BIO card.