OPO TEC Controller Servo Settings

The OPO TEC controller settings were changed to have a faster and stabler servo.

These coefficients are from LLO, which should work for both in-air and in-vacuum.

Loop Shape:

Gain: 700e-3   UGF: 60e-3 Hz

  Zeros(Hz) Poles(Hz)
 #1  -1(disabled) 1
 #2 10e-3 100e-3
 #3 10e-3 0
 #4 10e-3 0

 

Before:

Gain: 300e-3   UGF: 60e-3 Hz

  Zeros(Hz) Poles(Hz)
 #1  -1(disabled) 1
 #2 10e-3 100e-3
 #3 10e-3 -1
 #4 30e-3 0
Images attached to this report