kyle.ryan@LIGO.ORG - posted 14:20, Thursday 23 December 2010 (436)
Mid & End buildings, CP7 dewar vapor pressure
Toured through Mid and End buildings, chiller yards and dewars.  

Vapor pressure for CP7 LN2 dewar still 0 psig->Fully closed economizer regulator adjusting screw, tapped regulator body, turned out adjuster screw 6 turns ccw.  Also, closed QDP80 shaft purge (LN2 boil-off) valve at QDP80.  