Displaying report 1-1 of 1.
Reports until 10:11, Tuesday 18 December 2018
H1 PEM
jeffrey.bartlett@LIGO.ORG - posted 10:11, Tuesday 18 December 2018 (46036)
Monthly Dust Monitor Vacuum Pump Checks (FAMIS #7930)

    All three vacuum pumps (EY, EX, CS) are running well. Temperatures were all less than 150f. Made air bleed adjustments at End-X and the corner station.

   Note: There is carbon dust accumulation on the muffler and the output filter port on the corner station pump. This is a sign of late stage wear on the vanes. There is no spare for this pump, so it will need rebuilding in the near future.

   Closing FAMIS #7930