Displaying report 1-1 of 1.
Reports until 21:35, Saturday 23 February 2019
H1 PSL
sheila.dwyer@LIGO.ORG - posted 21:35, Saturday 23 February 2019 - last comment - 08:44, Sunday 24 February 2019(47103)
FSS oscillation threshold

The guardian that toggles the FSS gain when it is oscillating has not been toggling it, which is why it has sometimes been taking a long time to lock the FSS and IMC.  The reason it wasn't working was that it relies on H1:PSL-FSS_OSCILLATION to check if the FSS is oscilating, which wasn't working.  I reset the threshold for that from 5V to 0.2V, and now the guardian is toggling the common gain to relock the FSS as it was meant to.  

Comments related to this report
peter.king@LIGO.ORG - 08:44, Sunday 24 February 2019 (47106)
Sorry, I forgot to change it back when I was checking things on Friday.
Displaying report 1-1 of 1.