Displaying report 1-1 of 1.
Reports until 18:38, Wednesday 24 April 2019
H1 GRD (GRD, ISC, OpsInfo)
corey.gray@LIGO.ORG - posted 18:38, Wednesday 24 April 2019 - last comment - 19:53, Wednesday 24 April 2019(48744)
Odd SUS BS SDF Diffs!!! (But Back To OBSERVING)

(Georgia, Corey)

After running an INITIAL ALIGNMENT, H1 locked up with not too many issues.  While at NLN, had some diffs (screenshot is attached):

1)  H1OAF

This was known, and Sheila said I should ACCEPT these.

2) SUS-BS_M1_LOCK_P stuff!

For some reason this filter bank had its Input OFF, the gain at 0 (vs -1), and the TRAMP was different.  There was also a TRAMP diff for M1_OPTICALIGN_P.  Georgia figured out that the issue was an error with guaridan for a Fast EZCA (i.e. "fez" step).  Basically:

  1. fez command ran a whole bunch of commands on a list of optics,
  2. Error occurs
  3. But guardian sort of continues but (maybe randomly) skips a handful of lines for H1:SUS-BS_M1_LOCK_P*.
  4. And then continues with the fez command. 

(see log for ISC_DRMI node below)

2019-04-25_00:15:36.433915Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-IM4_M1_LOCK_Y_TRAMP => 5
2019-04-25_00:15:36.434484Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-IM4_M1_LOCK_Y_GAIN => 0
2019-04-25_00:15:36.435067Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-IM4_M1_OPTICALIGN_Y_TRAMP => 5
2019-04-25_00:15:36.435459Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] waiting for ramps to finish...
2019-04-25_00:15:41.447834Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] done waiting
2019-04-25_00:15:41.453307Z Traceback (most recent call last):
2019-04-25_00:15:41.453307Z   File "_ctypes/callbacks.c", line 315, in 'calling callback function'
2019-04-25_00:15:41.466866Z   File "/usr/lib/python2.7/dist-packages/epics/ca.py", line 583, in _onConnectionEvent
2019-04-25_00:15:41.467296Z     if int(ichid) == int(args.chid):
2019-04-25_00:15:41.467296Z TypeError: int() argument must be a string or a number, not 'NoneType'

2019-04-25_00:15:41.492347Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-BS_M1_LOCK_Y_RSET => 2
2019-04-25_00:15:41.493127Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-BS_M1_LOCK_Y_SW1 => 4
2019-04-25_00:15:41.532661Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-PR2_M1_LOCK_P_RSET => 2
2019-04-25_00:15:41.533281Z ISC_DRMI [OFFLOAD_DRMI_ASC.main] ezca: H1:SUS-PR2_M1_LOCK_P_SW1 => 4

Tonight's Solution:  For this lock, Georgia Turned ON the input, increased the TRAMP from 5 to 10, and then changed the gain from 0 to -1.0.

This cleared our SDF Diffs issue, and we then had a signal for H1:ASC-MICH_P_OUT16 (it had been 0 due to the gain of 0).

Conclusion:  We are back to OBSERVING.  But we are curious about whether this will occur for the next lock.
(If this happens again for BS_M1 Pitch, follow the steps for "Tonight's Solution" above until it can be fixed.)

Images attached to this report
Comments related to this report
georgia.mansell@LIGO.ORG - 19:53, Wednesday 24 April 2019 (48747)

Sheila weeded calls to fast ezca out of ISC_LOCK and ISC_DRMI, because of the problem Corey describes above. This instance snuck through as it is hidden in ISC_GEN_STATES, in the gen_OFFLOAD_ALIGNMENT_MANY state.

What happened today is there was a connection error to some channel, and the beamsplitter top mass LOCK filter never got switched back on. Amazingly, we still acquired lock.

I have updated ISC_GEN_STATES, removing the fez. I think we need to reload the ISC_DRMI and ALIGN_IFO guardians to implement the new guardian code. I only updated the lines about fez, but the code is untested and I'm not very confident in my python/guardian skills, so I'm attaching the code for ISC_GEN_STATES.py as it was before my changes. If guardian complains upon reloading or relocking, and there isn't an obvious typo my changes can be reverted by replacing

    /opt/rtcds/userapps/release/isc/h1/guardian/ISC_GEN_STATES.py

with what I've attached here, and re-re-loading.