Displaying report 1-1 of 1.
Reports until 03:09, Wednesday 08 May 2019
H1 General (CDS)
corey.gray@LIGO.ORG - posted 03:09, Wednesday 08 May 2019 - last comment - 03:09, Wednesday 08 May 2019(49093)
Multi-System Failure for H1! (edit: Dolphin Network failure for LVEA)

During the shift change, we had multiple things fail on us.  While I can remember going to list what we saw/noticed in order:

Images attached to this report
Comments related to this report
corey.gray@LIGO.ORG - 00:38, Wednesday 08 May 2019 (49094)

7:27 Beginning Dolphin recovery (Dave).

corey.gray@LIGO.ORG - 00:46, Wednesday 08 May 2019 (49096)
  • Talked with Dave and he said this is a Dolphin failure for the LVEA (except the PSL) with IPC errors for EX & EY
  • 7:27 Dave started models in this order:  SUS, SEI, ISC/LSC, OAF1
  • Model restarts would take systems to their save.snaps
  • Dave asked me to:
    • untrip Software Watchdogs
    • untrip SUS & SEI
  • Dave handed over to me and said I can start recovery & we can go from there.
  • If Dolphin network crashes again we will wait until morning (not call anyone).
  • ...recoverying all the watchdogs!
  • Still see lots of message on DIAG_MAIN (see screenshot from initial entry)
corey.gray@LIGO.ORG - 00:57, Wednesday 08 May 2019 (49098)
  • Reset all Software Watch Dogs.
  • Now moving on to Untripping SUS & SEI.
    • Order I will take are HAMs and then BSCs
    • For each chamber I will start with the (1) payloads (i.e. SUS), (2) HEPI, & (3) ISI
corey.gray@LIGO.ORG - 01:47, Wednesday 08 May 2019 (49099)

NOTEs:

  • Dave might not have received text about this, because I asked him when I called (but he said he was going to check).
  • Ops Overview:  OFI (SUS) at HAM5 button doesn't work
  • 8:09 Completed untripping SUS & SEI watchdogs

IMC was not locking.

  • Ran DOWN for IMC_LOCK
  • then it locked when I requested ACQUIRE.
  • set to LOCKED state with no issue.
  • 8:19 IMC restored

Moved on to Locking

  • Locking Arms Green
    • 8:17 No spot for X & ugly spot for Y
    • 8:21 ALSx came back all the way on its own!   ALSx restored (Y-arm no change)
    • 8:40 Y arm restored
      • During the model restart looks like ITMy's save.snap took the pit & yaw offsets to a different spot (see attached)
      • Restored ITMy pit/yaw offsets & now had flashes!
      • UNLOCKED and tweaked up flashes via ETMy
      • ALSy restored
  • Moving on to rest of locking & will not keep a log (unless I begin to have issues at later locking steps.  
  • At this point we appear to be restored from the Dolphin crash (atleast from an operator's perspective).
Images attached to this comment