Following the mysterious crash of the SUS IM model yesterday at 12:40pm (looks like a Dolphin or timing error, SUS IM model froze up, IOP model has hugh timing error, DAQ status 0x4000), we just restarted both models on the h1sush2b front end (h1iopsush2b and h1susim). The user model was burt restored to the safe.snap. The user watchdog continues to be tripped, so zero DAC drive throughout this restart.