Reports until 16:50, Thursday 13 December 2012
H1 CDS
david.barker@LIGO.ORG - posted 16:50, Thursday 13 December 2012 (4924)
MX CP5 alarm reconfigured

a noisy signal for the MX CP5 LN2 level was causing constant alarms in the control room. I reconfigued the system such that the alarm will be raised only when the system is in alarm for 60 seconds.

ve.alhConfig file changed, HVE-MX:CP5_LT300 has COUNTERFILTER of 60. HSV for this PV set from MINOR to NO_ALARM.