Reports until 12:44, Tuesday 04 June 2019
H1 ISC (SQZ)
filiberto.clara@LIGO.ORG - posted 12:44, Tuesday 04 June 2019 - last comment - 14:47, Tuesday 04 June 2019(49648)
SQZ Controls Chassis 3 Modified

WP 8229
ECR E1900035
E1600386

Following Beckhoff terminals were added to SQZ Controls Chassis 3:

1. EL9410 QTY 2
2. EL3104
3. EL4132
4. EL1124
5. EL2124

New DB25 cable was pulled from SQZ-C1 rack in the CER to SQZ-R1 rack in the LVEA. Part of the AM modulated AOM amplifier installation, alog 48353.

F. Clara, R. McCarthy, M. Pirello, D. Sigg

Comments related to this report
daniel.sigg@LIGO.ORG - 14:47, Tuesday 04 June 2019 (49652)

The new interface is mostly working:

  • The power readback is 10dB too low right now (requires software restart)
  • The modulation bias input has a gain of 1/20 rather than 1 (requires hardware swap)
  • Errors are not pushed upwards (requires software restart)

This will be fixed during next maintenance.

Here is the new medm screen for the AM-modulated AOM driver.

Images attached to this comment