Reports until 15:40, Tuesday 04 June 2019
H1 CDS (CDS, PEM)
patrick.thomas@LIGO.ORG - posted 15:40, Tuesday 04 June 2019 - last comment - 16:48, Tuesday 04 June 2019(49653)
Corner station weather station moved to Vantage Pro 2
WP 8227

Daniel, Filiberto, Patrick, Richard

The code in PLC1 on h1ecatc1 was changed to use the Vantage Pro 2 library that I created prior. The weather station console was connected to port 2 (RS232 for channel 1) of an EP6002-0002 serial interface module. This module was named Corner MSR Weather and added to the end of the MSR Auxiliary device chain. A screenshot of the COM settings is attached.
Images attached to this report
Comments related to this report
patrick.thomas@LIGO.ORG - 16:48, Tuesday 04 June 2019 (49659)
Filiberto has added the wiring pin layout to the DCC as document D1900187.